Transformer Regulation
2V164-S Voltage Regulating & Tap Change Control Relay
제품특성uMATRIX PLATFORM
Large STN graphics LCD
System status LED indicators
Simple menu setting procedure
40-300V DC aux. supply
40-275V AC aux. supply
20-70V DC aux. Optional
Self diagnosis & fail alarm
Size 4M case
Made in Australia
The 2V16x Series relays are designed for the control of motor driven on-load power transformer tap changers. The 2V164-S Voltage Regulator Relay continuously monitors the transformer output voltage & current & provides “RAISE” & “LOWER” control commands to the on-load tap changer such that the load centre is automatically maintained within acceptable limits. Small variations in supply frequency will not affect the system performance. When designing the 2V164-S, considerable emphasis was placed on producing a relay which would be very simple to install, set up & operate in the field. The result is a simple yet effective & very dependable voltage regulator relay available at a competitive price. The relay is very easy to set up due to the large screen LCD HMI & PC programming port. RMS 2V164-S Relays have many in built features to simplify the interface with OLTC’s to provide a reliable, effective & simple to operate voltage control system.
Changes introduced on the 2V164-S
-
Case length reduced by 18mm to suit 4M56-S case;
-
LED backlighting to reduce EMC emissions – contrast adjustment no longer required;
-
Front panel USB programming port to increase data transfer speed and improve compatibility with notebook PC’s;
-
Network communications port is now optional to maintain low cost of base model;
-
Network communication port maintained the optically isolated RS485 serial port but the RS232 configuration option has been deleted;
-
New current and voltage channels to improve measurement stability;
-
New status input option covering 18-275V AC and 300V DC range;
-
Updated switchmode power supply to reduce EMC emissions and improve transient overload protection;
-
Surface mount production technology to allow increased component density for additional functionality now and in the future.
What has not changed from the 2V164
-
I/O and basic functionality has been maintained;
-
Basic menu structure and operation has been maintained;
-
Electrical terminal mapping has not changed allowing existing wiring diagrams to be maintained;
-
Compatibility with existing application software back to version 0500 maintained;
-
Compatibility with existing uMATRIXwin programming software maintained;
-
Modbus RTU network communication protocol maintained Case size 4 has been maintained although the length has been reduced.
-
Made in Australia