KUMSAN M&E Products (주)금산엠엔이는 고객 만족 및 가치 공유를 최우선으로 생각하며, 최고의 기술이 접목된 다양한 제품들을 수입/제조/공급하고 있습니다.

    Test Blocks & plug systems

    4M402 Flexible and high performance test block system

    제품특성
    Finger safe test sockets suit standard or shrouded type 4mm banana plugs for direct access to the protection or measurement scheme
    28 independent test groups may be specified with any combination of circuit types
    Automatic shorting of CT circuits completed in the test block – No test links or operator intervention required
    Isolation plug provides sequential circuit isolation timing in three (3) stages
    Clear and concise front panel circuit identification
    Test plug fitted with insertion handl

    The 4M402 Test Block is an evolution of our popular 4M300 system. The main difference is that each of the twenty eight (28) test groups may be specified at time of order to provide automatic CT shorting and sequential circuit isolation to suit specific protection schemes:

    • STAGE I Test Block Cover Extraction
      Isolation of Type 1 circuits
    • STAGE II Isolation Plug Extraction
      CT Shorting Automatic shorting of all CT circuits
      Isolation of Type 3 circuits
      Isolation of Type 2, 8 and 9 circuits
    • STAGE III Test Plug Insertion
      4mm Test Sockets available

    The main advantage of this approach is the improved level of safety and security afforded to the CT circuits. This is because the CT shorting function takes place within the 4M402 Test Block irrespective of the CT circuit position. In many test block systems the CT shorting is only accomplished when the Test Plug is inserted which leaves open the possibility of a CT circuit becoming open circuit due to the CT shorting links being omitted or in the wrong position. This potential problem is negated in the 4M402 and allows a single model 4M422 Test Plug to be employed for all 4M402 Test Block configurations.

    Each test circuit is connected to a separate pair of terminals at the rear of the case. During normal operation of the associated protection equipment, each terminal pair is connected via a circuit-shorting link.